budynki edukacyjne, ogrzewanie, moc cieplna, zapotrzebowanie na ciepło, zużycie ciepła
Abstrakt
This paper presents the selected results of examinations connected with a seasonal heat consumption (Q) and thermal power (q) for heating in educational buildings. The purpose of the analysis presented here was to examine the influence of possible occurrence and level of differences between the seasonal heat consumption (Q) and the seasonal heat demand (Qq) for heating, calculated on the basis of q values. A modification in the method for determination of Qq for room heating on the basis of available data on q was introduced. A linear function, describing the changes in (Qq – Q) depending on the changes in q values, which was applied for that purpose, made it possible to improve the consistency of obtained heat demand values in relation to measured consumption of heat for heating by 65.6%.
W artykule przedstawiono wybrane wyniki analiz związanych z sezonowym zapotrzebowaniem na ciepło (Q) i mocą szczytową (q) do ogrzewania budynków edukacyjnych. Celem tej analizy było ustalenie wystąpienia różnic pomiędzy sezonowym zużyciem ciepła (Q) a sezonowym zapotrzebowaniem na ciepło (Qq) do ogrzewania, obliczonym na podstawie znanej wartości szczytowej mocy cieplnej q. Realizacja ww. analizy stanowiła podstawę do zaproponowania zmiany w metodzie obliczania wartości zapotrzebowania na ciepło Qq do ogrzewania pomieszczeń na podstawie dostępnych danych. Wykorzystanie tutaj funkcji liniowej opisującej zmiany (Qq – Q) w zależności od zmian wartości q umożliwia zmniejszenie rozbieżności pomiędzy obliczonymi wartościami zapotrzebowania na ciepło a zmierzonym zużyciem ciepła do ogrzewania o 65,6%.
Klasyfikacja PKT
630000 Budownictwo
Wydział
Zbiory cyfrowe BPK
Licencja
Licencja PK
Prawa dostępu
Zasób dostępny dla wszystkich
Na stronie wykorzystywane są pliki cookie, bądź podobne rozwiązania. Aby poznać szczegóły zapoznaj się z polityką prywatności.