In the paper a different numerical approaches for seismic analysis of the power products have been presented. Main focus was put on typical simulation methods defined by IEEE and IEC standards. In many cases substations such as transformers are filled with oil. Standards do not provide clear information about fluid influence on power equipment during seismic event. Due to that fact some investigations related with fluid filled substations were done and summarized in this paper. Three different simulation methods were investigated: Fluid Structure Interaction (FSI) approach using FEM, CFD and code coupling software, acoustic approach and CEL (Coupled Euler Lagrange) method using Lagrange and Euler element formulation.
W artykule przestawiono różne podejścia numeryczne wykorzystywane do analiz sejsmicznych transformatorów. Głównie opisane metody symulacyjne, które są wskazane przez standardy IEEE oraz IEC. Jakkolwiek w tego typie produktach mamy często do czynienia z występującą tam cieczą, np. transformatory mocy a jego wpływ nie jest jasno określony przez powyższe standardy. W związku z powyższym trzy różne podejścia numeryczne do oszacowania wpływu cieczy na strukturę w produktach mocy zostały przedstawione. Są to: podejście oparte na metodzie Fluid Structure Interaction (FSI), podejście oparte na elementach akustycznych oraz podejście oparte na równaniach Lagange oraz Eulera (Coupled Euler Lagrange).
Wydział
Zbiory cyfrowe BPK
Licencja
Licencja PK. Brak możliwości edycji i druku.
Prawa dostępu
Zasób dostępny dla wszystkich
Na stronie wykorzystywane są pliki cookie, bądź podobne rozwiązania. Aby poznać szczegóły zapoznaj się z polityką prywatności.